C2 or C3? Making consistent EICR coding decisions

Two competent inspectors can look at the same installation and produce different reports. The gap is almost always at the C2 and C3 boundary, and it is the difference between a satisfactory report and a landlord facing 28 days of remedial work.

Updated 2026-09-30

What each code actually means

The codes describe risk, not age and not preference. Getting that straight removes most of the disagreement.

  • · C1 — danger present, risk of injury now. Immediate action required, and you tell the person responsible before you leave
  • · C2 — potentially dangerous. Safe as it stands, but a foreseeable fault or event would make it dangerous
  • · C3 — improvement recommended. Not dangerous and no fault would make it so, but it falls short of current standards
  • · FI — further investigation required. You cannot determine the risk without more work

The question that decides it

Ask: is there a single foreseeable failure or event that turns this observation into a danger? If yes, it is a C2. If the installation would still be safe after that event, it is a C3.

A missing earth at a metal light switch is a C2 — one insulation failure makes the faceplate live. No RCD on a lighting circuit in a modern house is a C3 — nothing about it becomes dangerous without a separate fault, and the circuit complied when installed.

Worked examples at the boundary

These are the cases that generate the most argument between inspectors and contractors.

  • · No RCD on a socket circuit likely to supply outdoor equipment: C2
  • · No RCD on an internal socket circuit in an unoccupied commercial unit: C3, sometimes C2 depending on use
  • · Plastic consumer unit in a domestic property, otherwise sound: C3
  • · Plastic consumer unit with signs of heat damage at the terminals: C1 or C2 depending on severity
  • · Missing supplementary bonding in a bathroom with no RCD protection: C2
  • · Missing supplementary bonding in a bathroom where all circuits are 30 mA RCD protected and main bonding is present: C3
  • · Cables buried less than 50 mm in a wall without mechanical protection or RCD: C2
  • · No circuit identification or schedule at the board: C3
  • · Exposed live conductors at a damaged accessory: C1

Age is not a code

An installation is inspected against the standard in force when it was installed, with current requirements used to judge safety. Something that was compliant in 1998 and remains safe is not automatically a C3, and it is certainly not a C2.

Writing 'does not comply with BS 7671:2018+A4:2026' against every rewireable fuse in a functioning installation inflates the report and damages trust in the profession.

What over-coding costs everybody

Coding a C3 as a C2 makes the report unsatisfactory. Under the Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020 that starts a 28-day remedial clock, and a landlord who does not comply faces penalties of up to £30,000.

It also invites a second opinion, and a report that is overturned follows you. Under-coding is worse still: if somebody is injured by something you saw and coded C3, you will be asked to justify it.

Using FI properly

FI is not a way to avoid a decision. It is for genuine cases where you cannot establish the risk — a circuit you could not test because it serves equipment that must not be switched off, or evidence of concealed damage you cannot access.

Under Amendment 4, FI is handled as an advisory outcome on the model forms, but any installation with an outstanding FI cannot be regarded as satisfactory until the investigation is complete.

Evidence and consistency

Photograph every observation. A picture attached to the report removes almost all argument about whether the code was justified, and Amendment 4 explicitly anticipates photographic and thermal imaging evidence being attached.

Write the observation in plain language, state the risk, and cite the regulation. 'No RCD protection to socket-outlets likely to supply equipment outdoors, risk of electric shock, Regulation 411.3.3' tells the reader everything. 'No RCD' does not.

Newsletter

Certi Trade Dispatch

A short monthly email for the trade: regulation changes, new best-practice guidance, fresh calculators and course dates. No spam, unsubscribe any time.

Frequently asked questions

Does a C3 make an EICR unsatisfactory?+

No. C3 is the only code that can appear on a satisfactory report. Any C1, C2 or FI makes the report unsatisfactory.

Is a plastic consumer unit a C2?+

Not on its own. In a domestic property it is normally a C3, because it complied when installed and is not dangerous. Signs of heat damage or poor terminations change that.

Is a missing bathroom supplementary bond always a C2?+

No. Where main protective bonding is present and every circuit in the location has 30 mA RCD protection, the conditions for omitting supplementary bonding are met and it is a C3 at most.

How long does a landlord have to fix a C2?+

28 days from the report, or sooner if the report specifies a shorter period, under the 2020 Private Rented Sector Regulations in England.

Can I change a code after issuing the report?+

You can issue a corrected report, but you must explain why. Frequent corrections suggest an inconsistent process, so make the decision carefully on site.

Should I quote for the remedial work myself?+

You can, and most clients expect it, but keep the inspection findings and the quotation as separate documents so there is no suggestion the coding was influenced by the work it generates.